Engineering Tools · Free HVAC Physics Calculators

HVAC Engineering Calculators for Uzbekistan & Kazakhstan Projects.

Verify baseline engineering physics before equipment selection: altitude air-density correction for Almaty and Tashkent, duct velocity and equivalent diameter, and chilled water or propylene-glycol flow.

Calculations use standard textbook physics (ISA atmosphere, continuity equation, fluid specific heat) for preliminary engineering checks. Final unit selection and +46...+50 C high-ambient derating must be verified against factory catalog tables.

Altitude Barometric Pressure & Air Density Correction

In Almaty (700-1,100 m ASL) and Samarkand (705 m), air density is 8-12% below sea-level standard (1.20 kg/m3). Check actual delivered static pressure and required catalog selection pressure.

Site air density1.141 kg/m3
Barometric pressure95.98 kPa
Density ratio (vs 1.20 kg/m3)0.95
Catalog selection pressure526 Pa
Actual site pressure at catalog Pa475 Pa
Mass-flow change vs sea level-5%

Duct Cross-Section, Air Velocity & Dynamic Pressure

Check round and rectangular duct air velocity, Huebscher equivalent diameter and aspect ratio before issuing 3D/BIM coordination layouts.

Air velocity6.67 m/s
Cross-section area0.15 m2
Equivalent diameter Deq420 mm
Dynamic pressure Pd25.4 Pa
Suggested round dia (~5 m/s)560 mm
Aspect ratio A/B1.67 : 1
Main trunk / riser velocity (5.5 - 8.5 m/s)

Chilled Water / Propylene Glycol Flow & Pipe DN Sizing

Switching from water to 40-50% propylene glycol (Astana and Almaty winter chiller/dry-cooler loops) lowers specific heat and increases required flow rate and pump head.

Volumetric flow43.01 m3/h
Flow in L/s11.95 L/s
Pipe fluid velocity1.37 m/s
Suggested DN (<= 1.8 m/s)DN 100
Flow increase vs water+0%
Freeze protection point0 °C
Optimal hydronic velocity (0.6 - 1.8 m/s)

Air Exchange Flow Rate & AHU Sensible Load / Heat Recovery

Estimate room ventilation airflow from floor area and air changes per hour (L = V x n), sensible heating or cooling load at site air density, and power saved by heat recovery.

Room volume V875 m3
Airflow rate L3500 m3/h
Flow in L/s972.2 L/s
Gross coil load (no recovery)22.3 kW
Heat recovery savings-13.38 kW
Net heating / cooling coil power8.92 kW
Specific load35.7 W/m2

HVAC Calculation Questions

Why must fans for Almaty be corrected for elevation?

At 850 m above sea level, air density at +20 C drops to ~1.09 kg/m3 compared to standard 1.20 kg/m3 (-9%). Fan static pressure and coil heat transfer scale down proportionally unless corrected at selection.

How does 40% propylene glycol affect chiller and pump sizing in Astana?

Propylene glycol has lower specific heat and higher viscosity than water, requiring higher volumetric flow (m3/h) and a larger pump head to deliver the same cooling load in kW.

Technical sections & tools

Need a full duty-point review of your HVAC schedule?

Open the Public Designer Workspace to browse AVZ and RØNIQ series or send your equipment schedule to Nekker Labs engineers.

Let’s start with your project.

Email your HVAC equipment schedule, 3D/BIM pilot drawings or supply enquiry for engineering review.

Write an email
Projects and partnershipsinfo@nekkerlabs.com
Contacts
Rinat BaitemirProjects & Partnerships
+90 501 552 29 11
Alexandr KlimenkoKazakhstan · Almaty
+7 701 742 72 92
Offices & addresses
01 · Uzbekistan · Tashkent

OOO Nekker Labs

Uzbekistan, Tashkent, Yunusabad District, Bogishamol Street, 260A

Rinat Baitemirinfo@nekkerlabs.com
02 · Kazakhstan · Almaty

TOO Nekker

Kazakhstan, Almaty, Bostandyk District, Arkhat Microdistrict, Denis Ten Street, 2

Alexandr Klimenko+7 701 742 72 92
04 · USA · Wyoming

Nekker Labs

1309 Coffeen Avenue, STE 1200, Sheridan, Wyoming 82801