Smoke Extraction, Pressurization & Parking Jet Ventilation Systems. We perform aerodynamic verification and supply complete life-safety ventilation packages: 400 C and 600 C (2-hour) smoke extraction fans, stairwell and elevator shaft pressurization units, enclosed parking impulse jet fans and EI fire/smoke dampers compliant with SHNK UZ and SN RK / SP RK.
Thermal Rating 400 C (2h) & 600 C (2h)
Fire / Smoke Dampers EI 60 · EI 90 · EI 120 · EI 180
Parkings & Atriums Impulse Jet Fans + Axial/Roof Smoke Fans
Factory Partner AVZ Lineup + Fire Control Panels
01 Specialty Hub 06 · Fire & Smoke Control Systems
End-to-End Life-Safety Ventilation Scope SMK-01 Roof, Centrifugal & Axial Smoke Extraction Fans Dependable smoke evacuation from corridors, mall atriums, high-rises and underground parkings.
Upblast and side-discharge roof smoke fans complete with insulated roof curbs, backdraft shutters and drip pans Centrifugal and inline/wall-mounted smoke extractors for dedicated fire-rated fan rooms Certified 400 C (120 min) and 600 C (120 min) constructions in carbon and heat-resistant steels SMK-02 Stairwell, Elevator Shaft & Refuge Area Pressurization Maintaining smoke-free egress routes when doors open on the fire floor.
Axial and centrifugal pressurization fans for elevator shafts, smoke-proof stairwells and fire-service airlocks Integrated electric supply-air preheaters engineered for Astana and Almaty winter conditions Barometric/motorized pressure relief dampers and VFD differential-pressure control holding 20-150 Pa SMK-03 Ductless Impulse (Jet) Ventilation for Underground Parkings Eliminating bulky horizontal ductwork while preserving clear vehicle headroom.
Unidirectional and reversible jet fans (30-100 N thrust) serving dual-mode daily CO dilution and fire smoke control Coordinated sequencing between jet fan zones, main exhaust shafts and CO / NOx gas detection 3D/BIM verification of jet throw envelopes clearing structural drop beams, sprinklers and signage SMK-04 Motorized Fire & Smoke Dampers Complete damper schedules for fire compartment walls and multi-story smoke shafts.
Normally-open fire dampers with thermal-fuse spring-return actuators (24V / 230V) Normally-closed wall and duct smoke dampers with reversible actuators and architectural grilles Dual-action and explosion-proof damper constructions for industrial and energy facilities 02 Project support
Pre-Order Life-Safety Engineering Checks System Element Critical Procurement Error Nekker Labs Verification Fire Commissioning Outcome Hot gas density (400/600 C) vs +20 C cold testing Sizing motor kW only for hot low-density gas causes breaker trips during +20 C commissioning tests Motor power verified for cold-air +20 C test density as well as fire duty point Clean start-up during fire-authority acceptance tests Actuator type (spring-return vs reversible) Ordering reversible actuators where code mandates fail-safe spring-return fire dampers Line-by-line audit of every damper function, EI rating and 24V/230V control voltage 100% compatibility with fire alarm matrix Door opening force & shaft overpressure (20-150 Pa) Fixed-speed fan over-pressurizes stairwell so occupants cannot push egress doors open Sizing pressure-relief dampers or differential-pressure VFD control loops Passes physical door-pull and Pa Differential tests Roof curb & shaft flange coordination Mismatched fan base flanges and clashes with roof parapets Matched factory fan + curb + damper assemblies verified in 3D Revit Fast crane rigging with zero rooftop steel rework
03 UZ · KZ
Smoke Control Supply Across Uzbekistan & Kazakhstan Equipping high-rise towers, shopping malls, airports, hotels, parkings and warehouses:
Tashkent Almaty Astana Samarkand Shymkent Bukhara Atyrau Aktau Karaganda Navoi
Equipment categories & engineering services UZ HVAC supply, chillers & 3D/BIM in Uzbekistan KZ HVAC supply, ventilation & 3D/BIM in Kazakhstan UZ-01 Tashkent & Tashkent Region (OOO Nekker Labs) KZ-01 Almaty & Foothill Hub (TOO Nekker) KZ-02 Astana & Northern Kazakhstan (-40 C Winter) UZ-02 Samarkand, Bukhara, Navoi & Fergana KZ-03 Shymkent, Atyrau & Aktau (Ex & Marine) 01 Ventilation, AHUs & smoke control (AVZ) 02 High-ambient +50 °C chillers, fan coils & cooling (RØNIQ) 03 Multi-zone VRF/VRV, rooftops & heat pumps 04 HVAC control panels, PICV valves & BMS hydronics 05 Duty-point selection & HVAC schedule audit 07 Hygienic Medical AHUs, Cleanrooms & HEPA Filtration 08 LiDAR Scan-to-BIM & As-Built LOD 500 + COBie 09 AVZ - Industrial Fans, Smoke Exhaust & Fire Dampers 10 RØNIQ Systems - +50 C Chillers, Fan Coils & Rooftops 11 Industrial Plant Ventilation & Data Center Cooling G-01 Chiller-Fan Coil vs VRF for Hotels, Offices & Malls G-02 Specifying +46...+50 C High-Ambient Chillers G-03 High-Elevation (700-1,000 m) Fan & AHU Correction G-04 Arctic AHUs & Glycol Loops for -40 C Winters G-05 Smoke Control (400/600 C) & EI Damper Checklist G-06 When 3D/BIM (LOD 400) & Scan-to-BIM Pay Off BIM 3D / BIM (LOD 300 - 500) 04 FAQ
Smoke Control & Fire Damper Questions What is the difference between 400 C and 600 C smoke extraction fans? Thermal classification (400 C for 2 hours vs 600 C for 2 hours) depends on calculated smoke gas temperatures for the compartment fire load (offices/apartments vs car parks/polymer storage). We match fan metallurgy and motor cooling strictly to the project fire engineering specification.
Do your deliveries include roof curbs, flexible high-temp connectors and factory-mounted damper actuators? Yes. We supply complete matched assemblies including insulated/uninsulated roof curbs, high-temperature flexible connectors and fire/smoke dampers with factory-fitted actuators.
Technical sections & tools Closer to
manufacturer data. Open the public Designer Workspace, browse engineering category guides or sign in to the project platform.