Engineering Guide 03 · Altitude & Seismic HVAC
Almaty Ventilation & AHUs: 700-1,000 m Altitude & Seismic Engineering. In Almaty and foothill zones, air is 8-12% less dense than sea level. Learn how to correct fan curves, coil heat transfer and 9-10 zone seismic joints before ordering.
Almaty Elevation 700 - 1,100 m ASL
Air Density (+20 C) 1.07 - 1.10 kg/m3 (vs 1.20)
Seismic Zone 9 - 10 under SN RK
Online Tool Altitude calculator at /en/calculators/
01 Engineering Guide 03 · Altitude & Seismic HVAC
Three Mandatory Corrections for Almaty Projects ALT-01 Fan Static Pressure Recalculation At constant RPM, fans produce lower static pressure in thinner foothill air.
To deliver 500 Pa on site at 1.09 kg/m3, select against sea-level catalog curves at ~550 Pa Use our free online altitude calculator (/en/calculators/) to compute the exact ratio for your elevation Add static-pressure margin for two-stage G4 + F7/F9 winter smog filtration ALT-02 Mass Flow & 3D/BIM Seismic Joint Detailing Heating and cooling coils transfer heat via mass flow (kg/h), not volume flow (m3/h).
Always enter true site elevation (800-1,000 m) into AHU selection software Coordinate flexible seismic expansion loops across building joints in Revit (LOD 350-400) 02 Project support
Elevation Effect on Air Density (+20 C) City / Elevation Pressure (kPa) Density (kg/m3) Catalog Pressure Multiplier Sea level (0 m) 101.3 kPa 1.204 kg/m3 1.00 (baseline) Tashkent (455 m) 96.0 kPa 1.141 kg/m3 1.05 (+5%) Samarkand (705 m) 93.1 kPa 1.107 kg/m3 1.08 (+8%) Almaty center (850 m) 91.5 kPa 1.088 kg/m3 1.10 (+10%)
03 UZ · KZ
Foothill & High-Elevation Markets Altitude correction is essential across:
Almaty Talgar Bishkek Samarkand Shymkent
Equipment categories & engineering services UZ HVAC supply, chillers & 3D/BIM in Uzbekistan KZ HVAC supply, ventilation & 3D/BIM in Kazakhstan UZ-01 Tashkent & Tashkent Region (OOO Nekker Labs) KZ-01 Almaty & Foothill Hub (TOO Nekker) KZ-02 Astana & Northern Kazakhstan (-40 C Winter) UZ-02 Samarkand, Bukhara, Navoi & Fergana KZ-03 Shymkent, Atyrau & Aktau (Ex & Marine) 01 Ventilation, AHUs & smoke control (AVZ) 02 High-ambient +50 °C chillers, fan coils & cooling (RØNIQ) 03 Multi-zone VRF/VRV, rooftops & heat pumps 04 HVAC control panels, PICV valves & BMS hydronics 05 Duty-point selection & HVAC schedule audit 06 Smoke Control 400/600 C, Pressurization & Jet Fans 07 Hygienic Medical AHUs, Cleanrooms & HEPA Filtration 08 LiDAR Scan-to-BIM & As-Built LOD 500 + COBie 09 AVZ - Industrial Fans, Smoke Exhaust & Fire Dampers 10 RØNIQ Systems - +50 C Chillers, Fan Coils & Rooftops 11 Industrial Plant Ventilation & Data Center Cooling G-01 Chiller-Fan Coil vs VRF for Hotels, Offices & Malls G-02 Specifying +46...+50 C High-Ambient Chillers G-04 Arctic AHUs & Glycol Loops for -40 C Winters G-05 Smoke Control (400/600 C) & EI Damper Checklist G-06 When 3D/BIM (LOD 400) & Scan-to-BIM Pay Off BIM 3D / BIM (LOD 300 - 500) 04 FAQ
Altitude HVAC Questions Does TOO Nekker recalculate AVZ fan and AHU schedules for Almaty elevation? Yes. Our Almaty office (+7 701 742 72 92, info@nekkerlabs.com) automatically verifies true site air density on every duty-point selection.
Technical sections & tools Closer to
manufacturer data. Open the public Designer Workspace, browse engineering category guides or sign in to the project platform.